Fundamental principle:
.png)
Technical index:
Power supply: +24Vdc, maximum 32V, maximum operating current<100mA;
Output: 4~20mA, maximum load Resistance 750Ω.
Vibration measurement:
Type of measurement: peak amplitude;
Measurement range: 400μmpk-pk, can be customized at customer's request;
Measurement frequency response: 6~400Hz, can be customized at customer's request;
Maximum measure acceleration: ±5g;
Non-linearity of amplitude: ≤±2%.
Temperature measurement:
Sensor: Pt100, length of connecting rod can be changed according to requirement;
Measurement range: -50~+150℃, can be customized at customer's request;
Exact measurement: ±0.5%×F.S.
Working temperature: -20℃~+70℃;
Storage temperature: -40℃~+100℃;
Humidity: 95%noncoagulating;
Weight: about 750g.
.jpg)
|